Battery Backup Sizing Calculator

How big a battery bank do you need for your load, autonomy, and battery type?
Battery Sizing

Required Battery Capacity

Required Wh = Load×Days / (DoD×Efficiency)   •   Required Ah = Required Wh / Voltage
2kWh/day, 1 day, 50% DoD (lead-acid), 12V
Same load, 90% DoD (lithium)
2kWh/day, 2 days, 50% DoD, 24V
Wh/day
days
%
V
%
Enter values and press Calculate.
Depth of Discharge (DoD) is how much of a battery's rated capacity you may safely use. Flooded/AGM lead-acid batteries are typically limited to 50% DoD for reasonable lifespan; lithium (LiFePO4) batteries commonly tolerate 80–90% DoD — which is why a lithium bank needs noticeably less rated capacity for the same usable energy.

Required Capacity vs Autonomy Days (live — updates with your inputs)

Why Battery Sizing Needs More Than Just "Load × Days"

The simplest possible battery sizing would be "load times days," but real batteries can't be run down to empty, and no system is perfectly efficient. Two corrections turn a naive estimate into a usable design number:

Putting both corrections together: Required Wh = (Load × Days) / (DoD × Efficiency), and dividing by your chosen bank voltage converts that into amp-hours (Ah), the unit battery capacity is usually rated in.

QuantityFormula / Typical Value
Required energyWh = (Load×Days) / (DoD×Efficiency)
Required amp-hoursAh = Wh / Bank Voltage
Lead-acid safe DoD∼50% (flooded/AGM), some deep-cycle up to 60-70%
Lithium (LiFePO4) safe DoD∼80–90%, sometimes rated to nearly 100%
Typical system efficiency85–95%

Once you know your required Ah, the next design steps are the Solar Panel Sizing calculator (panels to recharge this bank daily) and the Charge Controller Sizing calculator (matching a controller to your array and this battery voltage).

Real-World Applications & Fully-Explained Examples

Worked examples — explained in full

1. 2000 Wh/day load, 1 day autonomy, 50% DoD (lead-acid), 12 V bank, 90% efficiency. Required Wh=2000×1/(0.50×0.90)=2000/0.45≈4444.4 Wh. Required Ah=4444.4/12≈370.4 Ah — note this is nearly 2.2× the raw 2000 Wh load, purely from the DoD and efficiency corrections.
2. Same load, but 2 days of autonomy instead of 1. Required Wh=2000×2/0.45≈8888.9 Wh, Required Ah≈740.7 Ah — exactly double example 1, since required capacity scales linearly with autonomy days.
3. Same load and voltage as example 1, but a lithium bank at 90% DoD instead of 50%. Required Wh=2000/(0.90×0.90)≈2469.1 Wh, Required Ah≈205.8 Ah — a lithium bank needs only about 56% of the rated capacity a lead-acid bank needs for the identical usable energy, which is a major reason lithium systems can use physically smaller/lighter battery banks.
4. Example 1's load/DoD/efficiency, but a 24 V bank instead of 12 V. Required Wh is unchanged at 4444.4 Wh, but Required Ah=4444.4/24≈185.2 Ah — exactly half example 1's amp-hour figure, since doubling system voltage halves the current (and therefore the Ah rating) needed to store the same energy.
5. Converting example 1's Wh into kWh. 4444.4 Wh ÷ 1000 = 4.444 kWh — the unit most battery/inverter datasheets and specification sheets actually quote for larger systems.
6. Lead-acid vs lithium bank size, side by side. For the identical 2000 Wh/day, 1-day, 12 V, 90%-efficiency scenario: lead-acid (50% DoD) needs 370.4 Ah, while lithium (90% DoD) needs only 205.8 Ah — a direct, concrete illustration of why chemistry choice is one of the biggest levers in off-grid battery bank sizing.

Frequently Asked Questions

How do I calculate the battery capacity I need for solar backup?

Use Wh = (Daily Load × Autonomy Days) / (Depth of Discharge × System Efficiency), then divide by your battery bank's voltage to get amp-hours (Ah).

What is Depth of Discharge (DoD) and why does it matter?

DoD is the fraction of a battery's rated capacity that is safe to regularly use without significantly shortening its lifespan. A battery limited to 50% DoD needs roughly twice the rated capacity of one rated for 100% DoD, for the same usable energy.

What DoD should I use for lead-acid batteries?

50% is a common conservative figure for flooded and AGM lead-acid batteries used in regular cycling service; going deeper (60-80%) regularly can noticeably shorten cycle life, though occasional deeper discharges in an emergency are generally tolerated.

What DoD should I use for lithium (LiFePO4) batteries?

80-90% is typical and conservative for long cycle life; many LiFePO4 cells are rated for even deeper discharge, but leaving a small margin (rather than fully depleting to 0%) is still good practice for longevity.

How many days of autonomy should I plan for?

1-2 days is common for grid-backup or sunny-climate off-grid systems; 3+ days is often used in cloudy climates or for critical loads where reliability matters more than upfront cost, since more autonomy directly means a larger, more expensive battery bank.

Why does battery voltage affect the Ah rating needed?

Energy (Wh) = Voltage × Amp-hours, so for a fixed energy requirement, a higher system voltage needs proportionally fewer amp-hours. This is why larger systems often move to 24V or 48V battery banks — it reduces both the Ah rating needed and the current (and wiring size) at a given power level.

What system efficiency should I assume?

85-95% is typical, covering inverter conversion losses and the battery's own round-trip charge/discharge efficiency. Lithium batteries generally have higher round-trip efficiency than lead-acid, so the higher end of this range is more realistic for lithium systems.

Should I size for my average daily load or peak load?

Size battery capacity (Ah/kWh) for your average daily energy consumption over the autonomy period, but separately verify your inverter and wiring can handle your peak instantaneous power draw (see the Solar Inverter Sizing calculator) — these are two different sizing questions.

Is it bad to oversize a battery bank beyond the calculated minimum?

Generally not — extra capacity beyond the minimum increases your safety margin, reduces average DoD per cycle (extending battery life), and provides headroom for load growth, at the cost of higher upfront price. Significant oversizing mainly matters if it goes unused for long periods, which can affect lead-acid batteries' health if left at low states of charge.

How does this battery sizing interact with solar panel sizing?

This calculator tells you how much energy you need to store; the Solar Panel Sizing calculator (using the same daily load figure) tells you how much panel wattage is needed to actually recharge that battery bank each day — both are necessary parts of a complete off-grid design.

Does temperature affect usable battery capacity?

Yes — most battery chemistries (especially lead-acid) deliver noticeably less usable capacity in cold temperatures and can have reduced lifespan in very hot conditions, so systems in extreme climates often add extra margin beyond this calculator's room-temperature-based estimate.

Related Calculators

Solar Panel SizingCharge Controller SizingBattery Capacity CalculatorAll Calculators